Type |
N/A Indirect Dry Electric |
Electrical Hazardous Area Classification |
N/A Class I Division 1 EEx d IIB T3 94/9EC Group D / ATEX Zone 1 |
Vaporizer Approvals |
N/A Designed per American Society of Mechanical Engineers (ASME) European Conformity (CE) FM (U.S. and Canada) NEMKO Pressure Equipment Directive (PED) Marked (PED is per Module "H") |
Liquid Inlet Connection |
N/A All Vaporizers have a 3/4" FNPT Threaded Inlet Connection |
Liquid Outlet Connection |
N/A All Vaporizers have a 1" FNPT Threaded Outlet Connection |
Vaporization Capacity1 | N/A 240 kg/h120 gal/h10.9 MMBtu/hour |
Design Pressure |
N/A 250 psig17.2 barg |
Relief Valve Set Point |
N/A 250 psig17.2 barg |
Hydrostatic Test Pressure |
N/A 375 psig25.9 barg |
Shipping Weight |
N/A 170 lb77 kg |
Note for Electrical Connection |
N/A
FM version: 1" FNPT with 11-1/2" pitch threads NEMKO version: Requires transition from 1" FNPT to M32 female threads External Explosion Proof Box version: 1-1/4" FNPT |
Voltage |
N/A 120 V208 V220 V240 V380 V400 V415 V440 V480 V575 V |
Phase at 120 Volt (V) Voltage |
N/A 1 |
Phase at 208 Volt (V) Voltage |
N/A 1 3 |
Phase at 220 Volt (V) Voltage |
N/A 1 3 |
Phase at 240 Volt (V) Voltage |
N/A 1 3 |
Phase at 380 Volt (V) Voltage |
N/A 3 |
Phase at 400 Volt (V) Voltage |
N/A 3 |
Phase at 415 Volt (V) Voltage |
N/A 3 |
Phase at 440 Volt (V) Voltage |
N/A 3 |
Phase at 480 Volt (V) Voltage |
N/A 3 |
Phase at 575 Volt (V) Voltage |
N/A 3 |
Power at 380 Volt (V) Voltage |
N/A 25.1 kW |
Power at 400 Volt (V) Voltage |
N/A 27.8 kW |
Power at 415 Volt (V) Voltage |
N/A 29.9 kW |
Power at 440 Volt (V) Voltage |
N/A 25.1 kW |
Power at 480 Volt (V) Voltage |
N/A 29.9 kW |
Current at 380 Volt (V) Voltage |
N/A 38.1 A |
Current at 400 Volt (V) Voltage |
N/A 40.1 A |
Current at 415 Volt (V) Voltage |
N/A 41.6 A |
Current at 440 Volt (V) Voltage |
N/A 33 A |
Current at 480 Volt (V) Voltage |
N/A 36 A |
Shipping Length |
N/A 24 in610 mm |
Shipping Width |
N/A 19 in183 mm |
Shipping Height |
N/A 66 in1676 mm |
Note for Shipping Dimensions |
N/A Hermetic Relay Version: TX240 and TX320 using an external Explosion Proof Box, add 6" (153mm) to W and 7" (178mm) to L dimensions. Add 100 lbs (46kg) to each unit. |