Vaporization Type |
N/A No Flame (Catalytic Heater) |
Start-Up Electrical Direct Current (DC) Voltage1 | N/A 12 V |
Operating Electrical2 | N/A Self-Generated |
Electrical Class |
N/A Hazardous Locations (Zone 1) |
Environmental Range |
N/A -40 to 120 ºF-40 to 49 ºC |
Fuel Type |
N/A Any Liquefied Petroleum Gas (LPG) Blend Butane Propane |
Inlet Fuel Connection National Pipe Thread (NPT) Size |
N/A 1/4 in |
Maximum Inlet Regulated Pressure |
N/A 10 to 11 inWc |
Maximum Inlet Regulated Pressure (H20) |
N/A 254 to 279 mm |
Maximum Inlet Unregulated Pressure |
N/A 10 to 250 psig0.7 to 17.2 barg |
On/Off Activation Factory Settings |
N/A OFF at >80 PSIG (5.51 barg) ON at <70 PSIG (4.82 barg) Via Tank Pressure (Adjustable Set Point) |
Heat Input |
N/A 10,000 Btu/hr2520 kcal/h |
Added Vaporization to Tank at -20 Degree Fahrenheit (ºF) Temperature3 | N/A 0.5 MMBtu/hour |
Added Vaporization to Tank at -28 Degree Fahrenheit (ºF) Temperature4 | N/A 126,000 kcal/h |
Mounts to (US Tank) |
N/A 500 to 3,900 gal946 to 14,742 L |
Tank Diameter |
N/A 37 to 41 in940 to 1,041 mm |
Unit Weight |
N/A 65 lb30 kg |
Shipping Weight |
N/A 70 lb32 kg |
Shipping Length |
N/A 32 in839 mm |
Shipping Width |
N/A 23 in585 mm |
Shipping Height |
N/A 20 in381 mm |
Safety Monitoring (Per National Fire Protection Association (NFPA 58)) |
N/A
Tank Pressure: >160 PSIG (11.03 barg) - OFF - Manual Restart Required Tank Surface Temperature (2): >125 ºF (51.7 ºC) Upper Sensor: Reverts to Standby Mode Lower Sensor: OFF - Manual Restart Required Below Minimum Pilot Temperature: OFF - Manual Restart Required |