Items 65 Inch (in) Unit Length Second Sun Tank Heater
MODEL SS-30
65 Inch (in) Unit Length Second Sun Tank Heater
Price QUOTE
25 Inch (in) Unit Length Second Sun Tank Heater (MODEL SS-10)
MODEL SS-10
25 Inch (in) Unit Length Second Sun Tank Heater
Price QUOTE
Description N/A
Vaporization Type N/A No Flame (Catalytic Heater)
Start-Up Electrical Direct Current (DC) Voltage1 N/A 12 V
Operating Electrical2 N/A Self-Generated
Electrical Class N/A Hazardous Locations (Zone 1)
Environmental Range N/A -40 to 120 ºF-40 to 49 ºC
Fuel Type N/A Any Liquefied Petroleum Gas (LPG) Blend Butane Propane
Inlet Fuel Connection National Pipe Thread (NPT) Size N/A 1/4 in
Maximum Inlet Regulated Pressure N/A 10 to 11 inWc
Maximum Inlet Regulated Pressure (H20) N/A 254 to 279 mm
Maximum Inlet Unregulated Pressure N/A 10 to 250 psig0.7 to 17.2 barg
On/Off Activation Factory Settings N/A OFF at >80 PSIG (5.51 barg) ON at <70 PSIG (4.82 barg) Via Tank Pressure (Adjustable Set Point)
Heat Input N/A 30,000 Btu/hr7560 kcal/h N/A 10,000 Btu/hr2520 kcal/h
Added Vaporization to Tank at -20 Degree Fahrenheit (ºF) Temperature3 N/A 2.2 MMBtu/hour N/A 0.5 MMBtu/hour
Added Vaporization to Tank at -28 Degree Fahrenheit (ºF) Temperature4 N/A 550,000 kcal/h N/A 126,000 kcal/h
Mounts to (US Tank) N/A 1,000 to 12,000 gal3,785 to 45,425 L N/A 500 to 3,900 gal946 to 14,742 L
Tank Diameter N/A 41 to 84 in1,041 to 2,134 mm N/A 37 to 41 in940 to 1,041 mm
Unit Weight N/A 155 lb70 kg N/A 65 lb30 kg
Unit Length N/A 65 in1,651 mm N/A 25 in635 mm
Unit Width N/A 18.5 in470 mm
Unit Height N/A 9 in227 mm N/A 9 in228 mm
Shipping Weight N/A 175 lb75 kg N/A 70 lb32 kg
Shipping Length N/A 76 in1,931 mm N/A 32 in839 mm
Shipping Width N/A 26 in661 mm N/A 23 in585 mm
Shipping Height N/A 19 in483 mm N/A 20 in381 mm
Safety Monitoring (Per National Fire Protection Association (NFPA 58)) N/A Tank Pressure: >160 PSIG (11.03 barg) - OFF - Manual Restart Required

Tank Surface Temperature (2): >125 ºF (51.7 ºC)
Upper Sensor: Reverts to Standby Mode
Lower Sensor: OFF - Manual Restart Required

Below Minimum Pilot Temperature: OFF - Manual Restart Required
  • 1 Use vehicle battery and "jumper cables"
  • 2 Thermoelectric device creates voltage based on Delta T
  • 3 Second Sun adds vaporization capability to the ambient vaporization capability of the tank itself. Total vaporization becomes the sum of the "natural" + "added" vaporization.