Unit of Measure
Specifications
Type |
N/A Indirect Dry Electric |
Electrical Hazardous Area Classification |
N/A Class I Division 1 EEx d IIB T3 94/9EC Group D / ATEX Zone 1 |
Vaporizer Approvals |
N/A Designed per American Society of Mechanical Engineers (ASME) European Conformity (CE) FM (U.S. and Canada) NEMKO Pressure Equipment Directive (PED) Marked (PED is per Module "H") |
Liquid Inlet Connection |
N/A All Vaporizers have a 3/4" FNPT Threaded Inlet Connection |
Liquid Outlet Connection |
N/A All Vaporizers have a 1" FNPT Threaded Outlet Connection |
Vaporization Capacity1 | N/A 320 kg/h160 gal/h14.5 MMBtu/hour |
Design Pressure |
N/A 250 psig17.2 barg |
Relief Valve Set Point |
N/A 250 psig17.2 barg |
Hydrostatic Test Pressure |
N/A 375 psig25.9 barg |
Shipping Weight |
N/A 180 lb82 kg |
Note for Electrical Connection |
N/A
FM version: 1" FNPT with 11-1/2" pitch threads NEMKO version: Requires transition from 1" FNPT to M32 female threads External Explosion Proof Box version: 1-1/4" FNPT |
Electrical Data
Voltage |
N/A 120 V208 V220 V240 V380 V400 V415 V440 V480 V575 V |
Phase at 120 Volt (V) Voltage |
N/A 1 |
Phase at 208 Volt (V) Voltage |
N/A 1 3 |
Phase at 220 Volt (V) Voltage |
N/A 1 3 |
Phase at 240 Volt (V) Voltage |
N/A 1 3 |
Phase at 380 Volt (V) Voltage |
N/A 3 |
Phase at 400 Volt (V) Voltage |
N/A 3 |
Phase at 415 Volt (V) Voltage |
N/A 3 |
Phase at 440 Volt (V) Voltage |
N/A 3 |
Phase at 480 Volt (V) Voltage |
N/A 3 |
Phase at 575 Volt (V) Voltage |
N/A 3 |
Power at 380 Volt (V) Voltage |
N/A 39.3 kW |
Power at 400 Volt (V) Voltage |
N/A 36.6 kW |
Power at 415 Volt (V) Voltage |
N/A 39.3 kW |
Power at 440 Volt (V) Voltage |
N/A 39.4 kW |
Power at 480 Volt (V) Voltage |
N/A 39.4 kW |
Power at 575 Volt (V) Voltage |
N/A 39.2 kW |
Current at 380 Volt (V) Voltage |
N/A 59.7 A |
Current at 400 Volt (V) Voltage |
N/A 52.8 A |
Current at 415 Volt (V) Voltage |
N/A 54.8 A |
Current at 440 Volt (V) Voltage |
N/A 51.7 A |
Current at 480 Volt (V) Voltage |
N/A 47.4 A |
Current at 575 Volt (V) Voltage |
N/A 39.4 A |
Shipping Dimensions
Shipping Length |
N/A 24 in610 mm |
Shipping Width |
N/A 19 in183 mm |
Shipping Height |
N/A 66 in1676 mm |
Note for Shipping Dimensions |
N/A Hermetic Relay Version: TX240 and TX320 using an external Explosion Proof Box, add 6" (153mm) to W and 7" (178mm) to L dimensions. Add 100 lbs (46kg) to each unit. |
- 1 Vaporization capacity shown is nominal. Actual is impacted by LPG composition and pressure.